4.1.6 EXTRAS AND ADVANCED
Table 24: Monitoring of the advanced values
Index Monitoring value Unit Scale ID Description
V2.6.1 Drive Status Word 1 43
B1 = Ready
B2 = Run
B3 = Fault
B6 = Run Enable
B7 = Alarm Active
B10 = DC current in stop
B11 = DC brake active
B12 = Run Request
B13 = Motor Regulator Active
B15 = Brake Chopper Active
V2.6.2 Ready status 1 78
B0 = Run Enable high
B1 = No fault active
B2 = Charge switch closed
B3 = DC voltage within limits
B4 = Power manager initialised
B5 = Power unit is not blocking start
B6 = System software is not blocking start
V2.6.3
Application Status
Word1
1 89
B0 = Interlock 1
B1 = Interlock 2
B2 = Reserved
B3 = Ramp 2 active
B4 = Mechanical brake control
B5 = I/O A control active
B6 = I/O B control active
B7 = Fieldbus Control Active
B8 = Local control active
B9 = PC control active
B10 = Preset frequencies active
B11 = Jogging active
B12 = Fire Mode active
B13 = Motor Preheat active
B14 = Quick stop active
B15 = Drive stopped from keypad
V2.6.4
Application Status
Word2
1 90
B0 = Acc/Dec prohibited
B1 = Motor switch open
B5 = Jockey pump active
B6 = Priming pump active
B7 = Input pressure supervision (Alarm/
Fault)
B8 = Frost protection (Alarm/Fault)
B9 = Autocleaning active
V2.6.5 DIN Status Word 1 1 56
VACON · 94 MONITORING MENU
4