5.15 GROUP 3.15: MULTI-PUMP
Table 99: Multi-pump parameters
Index Parameter Min Max Unit Default ID Description
P3.15.1 Number of Motors 1 6 1 1001
P3.15.2 Interlock Function 0 1 1 1032
0 = Disabled
1 = Enabled
P3.15.3 Include FC 0 1 1 1028
0 = Disabled
1 = Enabled
P3.15.4 Autochange 0 1 1 1027
0 = Disabled
1 = Enabled
P3.15.5 Autochange Interval 0.0 3000.0 h 48.0 1029
P3.15.6
Autochange: Fre-
quency Limit
0.00 P3.3.1.2 Hz 25.00 1031
P3.15.7
Autochange: Motor
Limit
1 6 1 1030
P3.15.8 Bandwidth 0 100 % 10 1097
P3.15.9 Bandwidth Delay 0 3600 s 10 1098
P3.15.10 Motor 1 Interlock Varies Varies
DigIN
Slot0.1
426
OPEN = Not active
CLOSED = Active
P3.15.11 Motor 2 Interlock Varies Varies
DigIN
Slot0.1
427
See P3.15.10
P3.15.12 Motor 3 Interlock Varies Varies
DigIN
Slot0.1
428
See P3.15.10
P3.15.13 Motor 4 Interlock Varies Varies
DigIN
Slot0.1
429
See P3.15.10
P3.15.14 Motor 5 Interlock Varies Varies
DigIN
Slot0.1
430
See P3.15.10
P3.15.15 Motor 6 Interlock Varies Varies
DigIN
Slot0.1
486
See P3.15.10
M3.15.16
Overpressure Super-
vision
See the overpressure supervision parameters below.