Table 84: Timer 3
Index Parameter Min Max Unit Default ID Description
P3.12.8.1 Duration 0 72000 s 0 1493 See Timer 1.
P3.12.8.2 Timer 3
DigINSlot
0.1
449
See Timer 1.
P3.12.8.3 Assign to Channel 1494 See Timer 1.
5.13 GROUP 3.13: PID CONTROLLER
Table 85: PID controller basic settings
Index Parameter Min Max Unit Default ID Description
P3.13.1.1 PID Gain 0.00 1000.00 % 100.00 118
P3.13.1.2 PID Integration Time 0.00 600.00 s 1.00 119
P3.13.1.3 PID Derivation Time 0.00 100.00 s 0.00 132
P3.13.1.4
Process Unit Selec-
tion
1 38 1 1036
P3.13.1.5 Process Unit Min Varies Varies Varies 0 1033
P3.13.1.6 Process Unit Max Varies Varies Varies 100 1034
P3.13.1.7
Process Unit Deci-
mals
0 4 2 1035
P3.13.1.8 Error Inversion 0 1 0 340
0 = Normal (Feedback
< Setpoint -> Increase
PID output)
1 = Inverted (Feedback
< Setpoint -> Decrease
PID output )
P3.13.1.9 Dead Band Varies Varies Varies 0 1056
P3.13.1.10 Dead Band Delay 0.00 320.00 s 0.00 1057
VACON · 140 PARAMETERS MENU
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/