5.21 GROUP 3.21: PUMP CONTROL
Table 106: Auto-cleaning parameters
Index Parameter Min Max Unit Default ID Description
P3.21.1.1 Cleaning Function 0 1 0 1714
0 = Disabled
1 = Enabled
P3.21.1.2 Cleaning Activation
DigIN
Slot0.1
1715
P3.21.1.3 Cleaning Cycles 1 100 5 1716
P3.21.1.4
Clean Forward Fre-
quency
0.00 50.00 Hz 45.00 1717
P3.21.1.5 Clean Forward Time 0.00 320.00 s 2.00 1718
P3.21.1.6
Clean Reverse Fre-
quency
0.00 50.00 Hz 45.00 1719
P3.21.1.7 Clean Reverse Time 0.00 320.00 s 0.00 1720
P3.21.1.8
Cleaning Accelera-
tion Time
0.1 300.0 s 0.1 1721
P3.21.1.9
Cleaning Decelera-
tion Time
0.1 300.0 s 0.1 1722
Table 107: Jockey pump parameters
Index Parameter Min Max Unit Default ID Description
P3.21.2.1 Jockey Function 0 2 0 1674
0 = Not used
1 = PID sleep
2 = PID sleep (level)
P3.21.2.2 Jockey Start Level 0.00 100.00 % 0.00 1675
P3.21.2.3 Jockey Stop Level 0.00 100.00 % 0.00 1676
Table 108: Priming pump parameters
Index Parameter Min Max Unit Default ID Description
P3.21.3.1 Priming Function 0 1 0 1677
0 = Disabled
1 = Enabled
P3.21.3.2 Priming Time 0.0 320.00 3.0 1678
PARAMETERS MENU VACON · 161