5.2 GROUP 3.2: START/STOP SETUP
Table 38: Start/stop setup menu
Index Parameter Min Max Unit Default ID Description
P3.2.1
Remote Control
Place
0 1 0 * 172
0 = I/O control
1 = Fieldbus control
P3.2.2 Local/Remote 0 1 0 * 211
0 = Remote
1 = Local
P3.2.3 Keypad Stop Button 0 1 0 114
0 = Yes
1 = No
P3.2.4 Start Function 0 1 0 505
0 = Ramping
1 = Flying start
P3.2.5 Stop Function 0 1 0 506
0 = Coasting
1 = Ramping
PARAMETERS MENU VACON · 105