5.3 GROUP 3.3: REFERENCES
Table 39: Frequency reference parameters
Index Parameter Min Max Unit Default ID Description
P3.3.1.1
Minimum Frequency
Reference
0.00 P3.3.1.2. Hz 0.00 101
P3.3.1.2
Maximum Frequency
Reference
P3.3.1.1. 320.00 Hz
50.00 /
60.00
102
P3.3.1.3
Positive Frequency
Reference Limit
-320.0 320.0 Hz 320.00 1285
P3.3.1.4
Negative Frequency
Reference Limit
-320.0 320.0 Hz -320.00 1286
P3.3.1.5
I/O Control Refer-
ence A Selection
0 19 5 * 117
0 = Preset Frequency 0
1 = Keypad reference
2 = Fieldbus
3 = AI1
4 = AI2
5 = AI1+AI2
6 = PID reference
7 = Motor potentiome-
ter
8 = Joystick reference
9 = Jogging reference
10 = Block Out.1
11 = Block Out.2
12 = Block Out.3
13 = Block Out.4
14 = Block Out.5
15 = Block Out.6
16 = Block Out.7
17 = Block Out.8
18 = Block Out.9
19 = Block Out.10
P3.3.1.6
I/O Control Refer-
ence B Selection
0 9 4 * 131
PARAMETERS MENU VACON · 107