5.4 GROUP 3.4: RAMPS AND BRAKES SETUP
Table 47: Ramp 1 setup
Index Parameter Min Max Unit Default ID Description
P3.4.1.1 Ramp 1 Shape 0.0 100.0 % 0.0 500
P3.4.1.2 Acceleration Time 1 0.1 300.0 s 5.0 103
P3.4.1.3 Deceleration Time 1 0.1 300.0 s 5.0 104
Table 48: Ramp 2 setup
Index Parameter Min Max Unit Default ID Description
P3.4.2.1 Ramp 2 Shape 0.0 100.0 % 0.0 501
P3.4.2.2 Acceleration Time 2 0.1 300.0 s 10.0 502
P3.4.2.3 Deceleration Time 2 0.1 300.0 s 10.0 503
P3.4.2.4 Ramp 2 Selection Varies Varies
DigIN
Slot0.1
408
0 = OPEN
1 = CLOSED
Table 49: Start magnetisation parameters
Index Parameter Min Max Unit Default ID Description
P3.4.3.1
Start Magnetising
Current
0.00 IL A IH 517
0 = Disabled
P3.4.3.2
Start Magnetising
Time
0.00 600.00 s 0.00 516
Table 50: DC brake parameters
Index Parameter Min Max Unit Default ID Description
P3.4.4.1 DC Brake Current 0 IL A IH 507
0 = Disabled
P3.4.4.2
DC Braking Time at
Stop
0.00 600.00 s 0.00 508
P3.4.4.3
Frequency to Start
DC Braking at Ramp
Stop
0.10 10.00 Hz 1.50 515
PARAMETERS MENU VACON · 113
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/