If you make a selection of an analogue input signal, you see step 18. With other selections,
the wizard goes to step 19.
17
Set the signal range of the analogue input
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
18
Set a value for P3.13.1.8 Error Inversion
0 = Normal
1 = Inverted
19
Set a value for P3.13.2.6 Setpoint Source Selection See table Setpoints in Chapter 5.13 Group
3.13: PID controller
If you make a selection of an analogue input signal, you see step 21. With other selections,
the wizard goes to step 23.
If you set Keypad Setpoint 1 or Keypad Setpoint 2 for the value, the wizard goes directly to step
22.
20
Set the signal range of the analogue input
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
21
Set a value for P3.13.2.1 (Keypad Setpoint 1) and
P3.13.2.2 (Keypad Setpoint 2)
Depends on the range set in step 20.
22
Using the sleep function
0 = No
1 = Yes
If you give the value Yes for step 22, you see the next 3 steps. If you give the value No, the
wizard is completed.
23
Set a value for P3.34.7 Sleep Frequency Limit Range: 0.00…320.00 Hz
24 Set a value for P3.34.8 Sleep Delay 1 Range: 0…3000 s
25 Set a value for P3.34.9 Wake-up Level The range depends on the set process unit
The PID Control application wizard is completed.
2.5 MULTI-PURPOSE APPLICATION WIZARD
The application wizard helps you to set the basic parameters that are related to the
application.
To start the Multi-purpose application wizard, set the value Multi-purpose to parameter P1.2
Application (ID 212) in the keypad.
VACON · 58 WIZARDS