5.9 GROUP 3.9: PROTECTIONS
Table 65: General protections settings
Index Parameter Min Max Unit Default ID Description
P3.9.1.2
Response to External
Fault
0 3 2 701
0 = No action
1 = Alarm
2 = Fault (Stop accord-
ing to stop function)
3 = Fault (Stop by
coasting)
P3.9.1.3 Input Phase Fault 0 1 0 730
0 = 3-phase support
1 = 1-phase support
P3.9.1.4 Undervoltage Fault 0 1 0 727
0 = Fault stored in his-
tory
1 = Fault not stored in
history
P3.9.1.5
Response to Output
Phase Fault
0 3 2 702
P3.9.1.6
Response to Field-
bus Communication
Fault
0 5 3 733
0 = No action
1 = Alarm
2 = Alarm + preset fault
frequency (P3.9.1.13)
3 = Fault (Stop accord-
ing to stop function)
4 = Fault (Stop by
coasting)
P3.9.1.7
Slot Communication
Fault
0 3 2 734
P3.9.1.8 Thermistor Fault 0 3 0 732
P3.9.1.9 PID Soft Fill Fault 0 3 2 748
P3.9.1.10
Response to PID
Supervision Fault
0 3 2 749
P3.9.1.11
Response to External
PID Supervision
Fault
0 3 2 757
P3.9.1.12 Earth Fault 0 3 3 703
P3.9.1.13
Preset Alarm Fre-
quency
P3.3.1.1 P3.3.1.2 Hz 25.00 183
P3.9.1.14
Response to Safe
Torque Off (STO)
Fault
0 2 2 775
0 = No action
1 = Alarm
2 = Fault (Stop by
coasting)
VACON · 130 PARAMETERS MENU
5