Table 4: M1.31 Standard
Index Parameter Min Max Unit Default ID Description
1.31.1 Preset Frequency 1 P1.3 P1.4 Hz 10.0 105
1.31.2 Preset Frequency 2 P1.3 P1.4 Hz 15.0 106
1.31.3 Preset Frequency 3 P1.3 P1.4 Hz 20.0 126
1.4.2 LOCAL/REMOTE APPLICATION
Use the Local/Remote application when, for example, it is necessary to switch between 2
different control places.
To change between the Local and the Remote control place, use DI6. When Remote control is
active, you can give the start/stop commands from Fieldbus or from I/O terminal (DI1 and
DI2). When Local control is active, you can give the start/stop commands from the keypad.
For each control place, you can make a selection of the frequency reference from the
keypad, Fieldbus or I/O terminal (AI1 or AI2).
It is possible to configure all the drive outputs freely in all the applications. There are 1
analogue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the
basic I/O board.
QUICK STARTUP GUIDE VACON · 21