Table 39: Frequency reference parameters
Index Parameter Min Max Unit Default ID Description
P3.3.1.7
Keypad Control Ref-
erence Selection
0 19 2 * 121
0 = Preset Frequency 0
1 = Keypad
2 = Fieldbus
3 = AI1
4 = AI2
5 = AI1+AI2
6 = PID reference
7 = Motor potentiome-
ter
8 = Joystick
9 = Jogging reference
10 = Block Out.1
11 = Block Out.2
12 = Block Out.3
13 = Block Out.4
14 = Block Out.5
15 = Block Out.6
16 = Block Out.7
17 = Block Out.8
18 = Block Out.9
19 = Block Out.10
P3.3.1.8
Keypad Reference P3.3.1.1 P3.3.1.2. Hz 0.00 184
P3.3.1.9 Keypad Direction 0 1 0 123
0 = Forward
1 = Reverse
P3.3.1.10
Fieldbus Control
Reference Selection
0 19 3 * 122
0 = Preset frequency 0
1 = Keypad
2 = Fieldbus
3 = AI1
4 = AI2
5 = AI1+AI2
6 = PID reference
7 = Motor potentiome-
ter
8 = Joystick
9 = Jogging reference
10 = Block Out.1
11 = Block Out.2
12 = Block Out.3
13 = Block Out.4
14 = Block Out.5
15 = Block Out.6
16 = Block Out.7
17 = Block Out.8
18 = Block Out.9
19 = Block Out.10
* = The selection of the application with parameter P1.2 Application gives the default value.
See the default values in Chapter 12 Appendix 1.