Table 86: Setpoint settings
Index Parameter Min Max Unit Default ID Description
P3.13.2.6
Setpoint source 1
selection
0 32 3 * 332
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
17 = Temperature input
1
18 = Temperature input
2
19 = Temperature input
3
20 = Temperature input
4
21 = Temperature input
5
22 = Temperature input
6
23 = Block Out.1
24 = Block Out.2
25 = Block Out.3
26 = Block Out.4
27 = Block Out.5
28 = Block Out.6
29 = Block Out.7
30 = Block Out.8
31 = Block Out.9
32 = Block Out.10
P3.13.2.7
Setpoint 1 minimum -200.00 200.00 % 0.00 1069
P3.13.2.8 Setpoint 1 maximum -200.00 200.00 % 100.00 1070
P3.13.2.9 Setpoint 1 boost -2.0 2.0 x 1.0 1071
P3.13.2.10
Setpoint source 2
selection
0 22 2 431
See P3.13.2.6.
P3.13.2.11 Setpoint 2 minimum -200.00 200.00 % 0.00 1073 See P3.13.2.7.
P3.13.2.12 Setpoint 2 maximum -200.00 200.00 % 100.00 1074 See P3.13.2.8.
P3.13.2.13 Setpoint 2 boost -2.0 2.0 x 1.0 1078 See P3.13.2.9.
VACON · 142 PARAMETERS MENU