Table 3: M1 Quick Setup
Index Parameter Min Max Unit Default ID Description
1.2 Application 0 5 0 212
0 = Standard
1 = Local/Remote
2 = Multi-Step Speed
3 = PID Control
4 = Multi-Purpose
5 = Motor Potentiome-
ter
1.3
Minimum Frequency
Reference
0.00 P1.4 Hz 0.0 101
1.4
Maximum Frequency
Reference
P1.3 320.0 Hz
50.0 /
60.0
102
1.5 Acceleration Time 1 0.1 300.0 s 5.0 103
1.6 Deceleration Time 1 0.1 300.0 s 5.0 104
1.7 Motor Current Limit I
H
*0.1 I
S
A Varies 107
1.8 Motor Type 0 2 0 650
0 = Induction Motor
1 = Permanent Magnet
Motor
2 = Reluctance Motor
1.9
Motor Nominal Volt-
age
Varies Varies V Varies 110
Find this value U
n
on
the nameplate of the
motor.
NOTE!
Find out if the motor
connection is Delta or
Star.
1.10
Motor Nominal Fre-
quency
8.0 320.0 Hz 50 / 60 111
Find this value f
n
on
the nameplate of the
motor.
1.11
Motor Nominal
Speed
24 19200 Rpm Varies 112
Find this value n
n
on
the nameplate of the
motor.
1.12
Motor Nominal Cur-
rent
I
H
* 0.1 I
H
* 2 A Varies 113
Find this value I
n
on
the nameplate of the
motor.
1.13
Motor Cos Phi
(Power Factor)
0.30 1.00 Varies 120
Find this value on the
nameplate of the
motor.
VACON · 18 QUICK STARTUP GUIDE