EasyManua.ls Logo

Vacon 100 INDUSTRIAL - Page 192

Vacon 100 INDUSTRIAL
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 121: Fieldbus Control Word
Bit
Descriptions
Value = 0 (FALSE) Value = 1 (TRUE)
Bit 0 Stop request from Fieldbus Start request from Fieldbus
Bit 1 Forward direction request Reverse direction request
Bit 2
No action Reset active faults and alarms (on rising
edge 0=>1)
Bit 3 No action Force stop mode to Coasting
Bit 4 No action Force stop mode to Ramping
Bit 5
No action
(normal deceleration ramp time)
Force drive to use fast deceleration ramp
time
(1/3 of normal deceleration time)
Bit 6 No action Freeze drive frequency reference
Bit 7 No action Force Fieldbus frequency reference to zero
Bit 8
No action Force drive control place to Fieldbus con-
trol
Bit 9
No action Force drive reference source to Fieldbus
reference
Bit 10
No action Jogging Reference 1 activation
NOTE!
This will start the drive.
Bit 11
No action Jogging Reference 2 activation
NOTE!
This will start the drive.
Bit 12
No action Activate Quick Stop function
NOTE!
This will stop the drive according to set-
ting in parameter menu M3.9.5.
Bit 13 Reserved Reserved
Bit 14 Reserved Reserved
Bit 15 Reserved Reserved
VACON · 192 MONITORING VALUE DESCRIPTIONS
9
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/

Table of Contents

Other manuals for Vacon 100 INDUSTRIAL

Related product manuals