C
B
E
D
A
Un
U[V]
f[Hz]
ID603
ID602
Fig. 23: Linear and squared change of the motor voltage
A. Default: Nominal voltage of the motor
B. Field weakening point
C. Linear
D. Squared
E. Default: Nominal frequency of the motor
C
BA
P1
P2
P3
ID604
ID605
ID606
Un
ID603
ID602
U[V]
f[Hz]
Fig. 24: The programmable U/f curve
A. Default: Nominal voltage of the motor
B. Field weakening point
C. Default: Nominal frequency of the motor
When the parameter Motor Type has the value PM motor (Permanent Magnet Motor), this
parameter is automatically set to the value Linear.