Fig. 54: The prohibited frequencies
A. Actual Reference
B. High Lim
C. Low lim
D. Requested Reference
P3.7.7 RAMP TIME FACTOR (ID 518)
Use this parameter to set the multiplier of the selected ramp times when the output
frequency of the drive is between the prohibited frequency limits.
The Ramp Time Factor sets the acceleration and the deceleration time when the output
frequency is in a prohibited frequency range. The value of the Ramp Time Factor is multiplied
with the value of P3.4.1.2 (Acceleration Time 1) or P3.4.1.3 (Deceleration Time 1). For
example, the value 0.1 makes the acceleration/deceleration time ten times shorter.
A
B
C
D
E
F
[s]
[Hz]
Fig. 55: The parameter Ramp Time Factor
A. Output Frequency
B. High Lim
C. Low Lim
D. Ramp Time Factor = 0.3
E. Ramp Time Factor = 2.5
F. Time
VACON · 270 PARAMETER DESCRIPTIONS