Fault
code
Fault ID Fault name Possible cause How to correct the fault
100 1100 Soft fill timeout There is a timeout in the
Soft fill function in the PID
controller. The process
value was not achieved in
the time limit.
A pipe that broke can be the
cause.
Do a check of the process.
Do a check of the parameters in
the menu M3.13.8.
101 1101 Feedback supervision
fault (PID1)
The PID controller: the feed-
back value is not in the
supervision limits (P3.13.6.2
and P3.13.6.3) and the delay
(P3.13.6.4), if you set the
delay.
Do a check of the process.
Do a check of the parameter set-
tings, the supervision limits and
the delay.
105 1105 Feedback supervision
fault (ExtPID)
The external PID controller:
the feedback value is not in
the supervision limits
(P3.14.4.2 and P3.14.4.3)
and the delay (P3.14.4.4), if
you set the delay.
109 1109 Input pressure super-
vision
The supervision signal of the
input pressure (P3.13.9.2) is
lower than the alarm limit
(P3.13.9.7).
Do a check of the process.
Do a check of the parameters in
menu M3.13.9.
Do a check of the input pressure
sensor and connections.
1409 The supervision signal of the
input pressure (P3.13.9.2) is
lower than the fault limit
(P3.13.9.8) .
111 1315 Temperature fault 1 1 or more of the tempera-
ture input signals (set in
P3.9.6.1) is higher than the
alarm limit (P3.9.6.2).
Find the cause of the temperature
rise.
Do a check of the temperature
sensor and connections.
If no sensor is connected, make
sure that the temperature input is
hardwired.
See the option board manual for
more data.
1316 1 or more of the tempera-
ture input signals (set in
P3.9.6.1) is higher than the
fault limit (P3.9.6.3).
112 1317 Temperature fault 2 1 or more of the tempera-
ture input signals (set in
P3.9.6.5) is higher than the
fault limit (P3.9.6.6).
1318 1 or more of the tempera-
ture input signals (set in
P3.9.6.5) is higher than the
fault limit (P3.9.6.7).
118 1118 AHF Over Temp The advanced harmonic fil-
ter function has caused an
overtemperature fault
through a digital input.
Do a check of the advanced har-
monic filter function.
FAULT TRACING VACON · 349