Table 16: M1.35 Multi-purpose
Index Parameter Min Max Unit Default ID Description
1.35.1 Control Mode 0 2 0 600
0 = U/f Freq Control
open loop
1 = Speed control open
loop
2 = Torque Control
open loop
1.35.2 Auto Torque Boost 0 1 0 109
0 = Disabled
1 = Enabled
1.35.3 Acceleration Time 2 0.1 300.0 s 10.0 502
1.35.4 Deceleration Time 2 0.1 300.0 s 10.0 503
1.35.5 Preset Frequency 1 P1.3 P1.4 Hz 5.0 105
1.35.6 U/f Ratio Select 0 2 0 108
0 = Linear
1 = Squared
2 = Programmable
1.35.7
Field Weakening
Point Frequency
8.00 P1.4 Hz Varies 602
1.35.8
Voltage at Field
Weakening Point
10.00 200.00 % 100.00 603
1.35.9
U/f Midpoint Fre-
quency
0.0 P1.35.7 Hz Varies 604
1.35.10 U/f Midpoint Voltage 0.0 100.00 % 100.0 605
1.35.11
Zero Frequency Volt-
age
0.00 40.00 % Varies 606
1.35.12
Start Magnetizing
Current
0.00 Varies A Varies 517
1.35.13
Start Magnetizing
Time
0.00 600.00 s 0.00 516
1.35.14 DC Brake Current Varies Varies A Varies 507
0 = Disabled
1.35.15
DC Braking time at
stop
0.00 600.00 s 0.00 508
1.35.16
Frequency to start
DC braking at ramp
stop
0.10 50.00 % 0.00 515