EasyManua.ls Logo

Vacon 100 INDUSTRIAL - Page 61

Vacon 100 INDUSTRIAL
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
feedback / one setpoint mode. The default control place is I/O A, and the default process unit
is %.
1 Set a value for P3.13.1.4 Process Unit Selection More than 1 selection.
If your selection is other than %, you see the next steps. If your selection is %, the wizard
goes directly to step 5.
2 Set a value for P3.13.1.5 Process Unit Min Varies
3 Set a value for P3.13.1.6 Process Unit Max Varies
4 Set a value for P3.13.1.7 Process Unit Decimals 0...4
5
Set a value for P3.13.3.3 Feedback 1 Source Selec-
tion
See the table Feedback settings in Chapter
5.13 Group 3.13: PID controller.
If you make a selection of an analogue input signal, you see step 6. With other selections, the
wizard goes to step 7.
6
Set the signal range of the analogue input
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
See table Analogue inputs in Chapter 5.5
Group 3.5: I/O configuration.
7
Set a value for P3.13.1.8 Error Inversion
0 = Normal
1 = Inverted
8
Set a value for P3.13.2.6 Setpoint Source 1 Selection See table Setpoints in Chapter 5.13 Group
3.13: PID controller.
If you make a selection of an analogue input signal, you see step 9. With other selections, the
wizard goes to step 11.
If you set Keypad Setpoint 1 or Keypad Setpoint 2 for the value, you see step 10.
9
Set the signal range of the analogue input
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
See table Analogue inputs in Chapter 5.5
Group 3.5: I/O configuration.
10
Set a value for P3.13.2.1 (Keypad setpoint 1) and
P3.13.2.2 (Keypad setpoint 2)
Varies
11
Using the sleep function
No
Yes
If you give the value Yes in step 11, you see the next 3 steps.
WIZARDS VACON · 61
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
2

Table of Contents

Other manuals for Vacon 100 INDUSTRIAL

Related product manuals