Parameters vacon • 107
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.6.4 Group 3.5.3: Digital outputs
Group 3.5.3.2: Slot B Basic
Table 80. Digital output settings on standard I/O board
Code Parameter Min Max Unit Default ID Description
P3.5.3.2.1 RO1 function 0 60 2 11001
Function selection for Basic R01:
0 = None
1 = Ready
2 = Run
3 = General fault
4 = General fault inverted
5 = General alarm
6 = Reversed
7 = At speed
8 = Thermistor fault
9 = Motor regulator active
10 = Start signal active
11 = Keypad control active
12 = I/O B control activated
13 = Limit supervision 1
14 = Limit supervision 2
15 = SinglePowerOn
16 = No function
17 = Preset speed active
18 = No function
19 = PID in Sleep mode
20 = PID soft fill active
21 = PID supervision limits
22 = Ext. PID superv. limits
23 = Input press. alarm/fault
24 = Frost prot. alarm/fault
25 - 30 = No function
31 = RTC time chnl 1 control
32 = RTC time chnl 2 control
33 = RTC time chnl 3 control
34 = FB ControlWord B13
35 = FB ControlWord B14
36 = FB ControlWord B15
37 = FB ProcessData1.B0
38 = FB ProcessData1.B1
39 = FB ProcessData1.B2
40 = Maintenance alarm
41 = Maintenance fault
42 = No function
43 = No function
54 -55 = No function
56 = Auto-cleaning
active
57 = Motor Switch
Open
58 = TEST (Always
Closed)
59 = No function
60 = DualSupply AC switch
M3.5.3.2.2 Basic R01 ON delay 0.00 320.00 s 0.00 11002 ON delay for relay
M3.5.3.2.3 Basic R01 OFF delay 0.00 320.00 s 0.00 11003 OFF delay for relay
M3.5.3.2.4 Basic R02 function 0 59 3 11004 See P3.5.3.2.1
M3.5.3.2.5 Basic R02 ON delay 0.00 320.00 s 0.00 11005 See M3.5.3.2.2.
M3.5.3.2.6 Basic R02 OFF delay 0.00 320.00 s 0.00 11006 See M3.5.3.2.3.