Parameters vacon • 91
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.1 Column explanations
Code = Location indication on the keypad; Shows the operator the parameter number.
Parameter= Name of parameter
Min = Minimum value of parameter
Max = Maximum value of parameter
Unit = Unit of parameter value; Given if available
Default = Value preset by factory
ID = ID number of the parameter
Description= Short description of parameter values or its function
= More information on this parameter available; Click the parameter name
7.1.2 Group 3.1: Motor settings
7.1.2.1 Group 3.1.1: Motor nameplate
7.1.2.2 Group 3.1.2: Motor Control
Table 59. Motor nameplate parameters
Code Parameter Min Max Unit Default ID Description
P3.1.1.1 Motor Nom Voltg Varies Varies V Varies 110
Find this value U
n
on the rating
plate of the motor. Note also used
connection (Delta/Star).
P3.1.1.2 Motor Nom Freq 8.00 320.00 Hz Varies 111
Find this value f
n
on the rating
plate of the motor.
P3.1.1.3 Motor Nom Speed 24 19200 rpm Varies 112
Find this value n
n
on the rating
plate of the motor.
P3.1.1.4 Motor Nom Currnt Varies Varies A Varies 113
Find this value I
n
on the rating
plate of the motor.
P3.1.1.5 Motor Cos Phi 0.30 1.00 0.74 120
Find this value on the rating plate
of the motor
P3.1.1.6 Motor Nom Power Varies Varies kW Varies 116
Find this value In on the rating
plate of the motor.
Table 60. Motor control
Code Parameter Min Max Unit Default ID Description
P3.1.2.1 Control mode 0 1 0 600
0 = U/f Freq ctrl open loop
1 = Speed control open loop
P3.1.2.2 Motor type 0 1 0 650
0 = Induction motor
1 = PM motor
P3.1.2.3 Switching Freq 1.5 Varies kHz Varies 601
Increasing the switching fre-
quency reduces the capacity of
the AC drive. It is recommended
to use a lower frequency when
the motor cable is long in order
to minimize capacitive currents
in the cable. Motor noise can
also be minimised using a high
switching frequency.