Parameters vacon • 161
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.2.12 Analog outputs
P3.5.4.1.1 AO1
FUNCTION
This parameter defines the content of the analogue output signal 1. The scaling of the analogue out-
put signal depends on the selected signal. See Table 144.
58
TEST (Always Closed)
59
No function
60
DualSupply AC switch
Table 144. AO1 signal scaling
Selection Selection name Description
0 Test 0% (Not used) Analogue output is forced either to 0% or 20% depending on
parameter P3.5.4.1.3.
1 TEST 100% Analogue output is forced to 100% signal (10 V / 20 mA).
2 Output frequency Actual output frequency from zero to MaxFreqReference.
3 Frequency reference Actual frequency reference from zero to MaxFreqReference.
4 Motor speed Actual motor speed from zero to Motor Nom Speed.
5 Output current Drive output current from zero to Motor Nom Currnt.
6 Motor torque Actual motor torque from zero to motor nominal torque (100%).
7 Motor power Actual motor power from zero to Motor Nom Power (100%).
8 Motor voltage Actual motor voltage from zero to Motor Nom Voltg.
9 DC-link voltage Actual DC-link voltage 0…1000 V.
10 PID output PID controller output (0…100%).
11 ExtPID output External PID controller output (0…100%).
12 Fieldbus Process Data In 1 Fieldbus Process Data In 1 from 0…10000 (corresponding
0…100.00%).
13 Fieldbus Process Data In 2 Fieldbus Process Data In 2 from 0…10000 (corresponding
0…100.00%).
14 Fieldbus Process Data In 3 Fieldbus Process Data In 3 from 0…10000 (corresponding
0…100.00%).
15 Fieldbus Process Data In 4 Fieldbus Process Data In 4 from 0…10000 (corresponding
0…100.00%).
16 Fieldbus Process Data In 5 Fieldbus Process Data In 5 from 0…10000 (corresponding
0…100.00%).
17 Fieldbus Process Data In 6 Fieldbus Process Data In 6 from 0…10000 (corresponding
0…100.00%).
18 Fieldbus Process Data In 7 Fieldbus Process Data In 7 from 0…10000 (corresponding
0…100.00%).
19 Fieldbus Process Data In 8 Fieldbus Process Data In 8 from 0…10000 (corresponding
0…100.00%).
Table 143. Output signals via RO1
Selection Selection name Description