vacon • 118 Parameters
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.11 Group 3.10: Automatic reset
7.1.12 Group 3.11: Appl. Settings
Table 95. Autoreset settings
Code Parameter Min Max Unit Default ID Description
P3.10.1 Automatic reset 0 1 0 731
0 = Disabled
1 = Enabled
P3.10.2 Wait time 0.10 10.0 m 1.0 717
Wait time before the first reset is
executed.
P3.10.3 Automatic reset tries 1 10 5 759
NOTE: Total number of trials (irre-
spective of fault type)
P3.10.4 Restart Function 0 1 1 719
We can choose what kind of start
function we want to use when
doing an autoreset of the drive.
0 = Flying start
1 = Start Function
P3.10.5
Underload reset Time
1
0.1 1200.0 m 2.0 1927
P3.10.6
Underload reset Time
2
0.1 1200.0 m 30.0 1928
P3.10.7
Underload reset Time
3
0.1 1200.0 m 300.0 1929
P3.10.8 Underload Tries T1,T2 1 10 2 1930
Table 96. Application Settings
Code Parameter Min Max Unit Default ID Description
P3.11.1 Parameter Password 0 9999 0 1806
P3.11.2 C/F selection 0 1 0 1197
0 = Celsius
1 = Fahrenheit
P3.11.3 kW/hp selection 0 1 0 1198
0 = kW
1 = hp
P3.11.4 Multimonitor View 0 2 1 1196
Division of keypad display into
sections in Multimonitor view.
0 = 2x2 sections
1 = 3x2 sections
2 = 3x3 sections
P3.11.5 FunctButtonConfig 0 15 15 1195
With this parameter it’s possible
to configure what alternatives are
visible when pressing the func-
tion button.