Parameters vacon • 141
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.2 Additional parameter information
Due to its user-friendliness and simplicity of use, the most parameters of the VACON
®
100 X Solar
Pump Application only require a basic description which is given in the parameter tables in chapter
7.1.
In this chapter, you will find additional information on certain most advanced parameters of the
VACON
®
100 X Solar Pump Application. Should you not find the information you need contact your
distributor.
7.2.1 Motor Control
P3.1.1.2 M
OTOR NOM FREQ
NOTE! When this parameter is changed, parameters P3.1.4.2 and P3.1.4.3 will be automatically ini-
tialized depending on the selected motor type. See Table 130.
P3.1.2.1 C
ONTROL MODE
P3.1.2.2 MOTOR TYPE
This parameter defines the used motor type.
When this parameter is changed, parameters P3.1.4.2 and P3.1.4.3 will be automatically initialized
according to the selected motor type.
See Table 130 for the initialization values:
Table 128.
Selection
number
Selection name Description
0
U/f control (open
loop)
Drive frequency reference is set to output frequency without slip com-
pensation. Motor actual speed is finally defined by motor load.
1
Speed control (open
loop)
Drive frequency reference is set to motor speed reference. The motor
speed is remains the same regardless of motor load. Slip is compen-
sated.
Table 129.
Selection
number
Selection name Description
0 Induction motor (IM) Select if an induction motor is used.
1
Permanent Magnet Synchronous
Motor (PMSM)
Select if a permanent magnet sychronous motor is used.
Table 130.
Parameter Induction Motor (IM)
Permanent Magnet Synchronous
Motor (PMSM)
P3.1.4.2
(Field WeakngPnt)
Motor nominal frequency Internally calculated
P3.1.4.3
(Voltage at FWP)
100,0% Internally calculated