7.1.16 Group 3.16: Mainten. Counters
The maintenance counter is a way of indicating the operator that maintenance needs to be carried
out. For example, a belt needs to be replaced or oil in a gearbox should be changed.
There are two different modes for the maintenance counters, hours or revolutions*1000. The
counters are only incremented during Run mode in either case. NOTE: Revolutions are based on
motor speed which is only an estimate (integration every second).
When the counter exceeds the limit an alarm or fault will be triggered respectively. Individual main-
tenance alarm and fault signals can be connected to a digital/relay output.
When maintenance has been carried out the counter can be reset through either a digital input or
a parameter B3.16.4.
Table 119. Maintenance counter parameters
Code Parameter Min Max Unit Default ID Description
P3.16.1 Counter 1 mode 0 2 0 1104
0 = Not used
1 = Hours
2 = Revolutions*1000
P3.16.2 Counter 1 alarm limit
214748
3647
80000 h/kRev 0 1105
When to trig a maintenance
alarm for counter 1.
0 = Not used
P3.16.3 Counter 1 fault limit
214748
3647
80000 h/kRev 0 1106
When to trig a maintenance fault
for counter 1.
0 = Not used
B3.16.4 Counter 1 reset 0 1 0 1107 Activate to reset counter 1.
P3.16.5 Counter 1 DI reset Varies Varies 0 490 TRUE = Reset