vacon • 86 Monitoring menu
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6.1.6 Timer functions
Here you can monitor values of timer functions and the Real Time Clock.
6.1.7 PID Controller
Table 51. Monitoring of timer functions
Code Monitoring value Unit Scale ID Description
V2.7.1 TC 1, TC 2, TC 3 1 1441
Possible to monitor the statuses of the three
Time Channels (TC)
V2.7.2 Interval 1 1 1442 Status of timer interval
V2.7.3 Interval 2 1 1443 Status of timer interval
V2.7.4 Interval 3 1 1444 Status of timer interval
V2.7.5 Interval 4 1 1445 Status of timer interval
V2.7.6 Interval 5 1 1446 Status of timer interval
V2.7.7 Timer 1 s 1 1447 Remaining time on timer if active
V2.7.8 Timer 2 s 1 1448 Remaining time on timer if active
V2.7.9 Timer 3 s 1 1449 Remaining time on timer if active
V2.7.10 Real time clock 1450 hh:mm:ss
Table 52. PID Controller value monitoring
Code Monitoring value Unit Scale ID Description
V2.8.1 PID setpoint Varies
According to
P3.13.1.7
20
PID controller setpoint value in process units.
Process unit is selected with a parameter.
V2.8.2 PID feedback Varies
According to
P3.13.1.7
21
PID controller feedback value in process units.
Process unit is selected with a parameter.
V2.8.3 PID error Varies
According to
P3.13.1.7
22
PID controller error value. Deviation of feedback
from setpoint in process units. Process unit is
selected with a parameter.
V2.8.4 PID output % 0.01 23
PID output in percent (0...100%). This value can
be fed e.g. to Motor Control (Frequency refer-
ence) or Analogue output
V2.8.5 PID status 1 24
0=Stopped
1=Running
3=Sleep mode
4=In dead band