EasyManua.ls Logo

Vacon 100 INDUSTRIAL - Sleep Function

Vacon 100 INDUSTRIAL
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters vacon • 171
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.2.18 Sleep Function
P3.13.5.1 S
LEEP FREQUENCY LIMIT 1
P3.13.5.2 SP 1 S
LEEP DELAY
P3.13.5.3 SP 1 WAKEUPLEVEL
This function will put the drive into sleep mode if the frequency stays below the sleep limit for a lon-
ger time than that set with the Sleep Delay (P3.13.5.2). This means that the start command remains
on, but the run request is turned off. When the actual value goes below, or above, the wake-up level
depending on the set acting mode the drive will activate the run request again if the start command
is still on.
Figure 64. Sleep limit, Sleep delay, Wake-up level
9098.emf
Actual value
Wake-up level
(ID1018)
Frequency
Sleep limit
(ID1016)
Sleep delay
(ID1017)
SleepRegulating mode Regulating mode