vacon • 132 Parameters
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.15 Group 3.14: ExtPID Controller
7.1.15.1 Group 3.14.1: Basic settings
For more detailed information, see chapter 7.1.14.
Table 114. Sleep - no demand detected
Code Parameter Min Max Unit Default ID Description
P3.13.10.1
Sleep No Demand
Detection Enable
0 1 0 1649
0 = No
1 = Yes
P3.13.10.2 SNDD Error Hysteresis 0 99999.9
P3.13.
1.4
0.5 1658
P3.13.10.3
SNDD Frequency Hys-
teresis
0.00 P3.3.1.2 Hz 3.00 1663
P3.13.10.4
SNDD Supervision
Time
0 600 s 120 1668
P3.13.10.5 SNDD Actual Add 0.00
P3.13.10.
2
P3.13.
1.4
0.5 1669
Table 115. Basic settings for external PID-controller
Code Parameter Min Max Unit Default ID Description
P3.14.1.1 Enable ExtPID 0 1 0 1630
0 = Disabled
1 = Enabled
P3.14.1.2 Start signal
DigIN
Slot0.2
1049
FALSE = PID2 in stop mode
TRUE = PID2 regulating
This parameter will have no effect
if PID2 controller is not enabled in
the Basic menu for PID2
P3.14.1.3 Output in Stop 0.0 100.0 % 0.0 1100
The output value of the PID con-
troller in % of its maximum output
value while it is stopped from digi-
tal input
P3.14.1.4 Gain 0.00 1000.00 % 100.00 1631
P3.14.1.5 Integration Time 0.00 600.00 s 1.00 1632
P3.14.1.6 Derivation Time 0.00 100.00 s 0.00 1633
P3.14.1.7 ProcessUnitSel. 0 37 0 1635
P3.14.1.8 ProcessUnitMin Varies Varies Varies 0 1664
P3.14.1.9 ProcessUnitMax Varies Varies Varies 100 1665
P3.14.1.10 ProcessUnitDeci 0 4 2 1666
P3.14.1.11 Error inversion 0 1 0 1636
P3.14.1.12 Dead Band Varies Varies Varies 0.0 1637
P3.14.1.13 Dead Band Delay 0.00 320.00 s 0.00 1638