Parameters vacon • 131
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
P3.13.9.2 Superv. Signal 0 13 Hz 0 1686
The source of input pressure
measurement signal:
0=Analogue input 1
1=Analogue input 2
2=Analogue input 3
3=Analogue input 4
4=Analogue input 5
5=Analogue input 6
6=ProcessDataIn1 (0-100%)
7=ProcessDataIn2 (0-100%)
8=ProcessDataIn3 (0-100%)
9=ProcessDataIn4 (0-100%)
10=ProcessDataIn5 (0-100%)
11=ProcessDataIn6 (0-100%)
12=ProcessDataIn7 (0-100%)
13=ProcessDataIn8 (0-100%)
P3.13.9.3 Superv. Unit Sel. 0 8 Varies 2 1687
Select unit for supervision. The
supervision signal (P3.13.9.2) can
be scaled to process units on the
panel.
P3.13.9.4 Superv. Unit Decimal 0 4 2 1688
Choose how many decimals to
show.
P3.13.9.5 Superv. Unit Min Varies Varies Varies Varies 1689 Unit min and max parameters are
the signal values corresponding
to e.g. 4mA and 20 mA respec-
tively (scaled linearly between
these).
P3.13.9.6 Superv. Unit Max Varies Varies Varies Varies 1690
P3.13.9.7 Superv. Alarm Level Varies Varies Varies Varies 1691
Alarm (Fault ID 1363) will be
launched if supervision signal
stays below the alarm level lon-
ger than the time defined by
parameter P3.13.9.9.
P3.13.9.8 Superv. Fault Level Varies Varies Varies Varies 1692
Fault (Fault ID 1409) will be
launched if supervision signal
stays below the fault level longer
than the time defined by parame-
ter P3.13.9.9.
P3.13.9.9 Superv. Fault Delay 0.00 60.00 s 5.00 1693
Delay time to launch the
Input
pressure supervision
alarm
or fault if the supervi-
sion signal stays below the
alarm/fault level longer than
defined by this parameter.
P3.13.9.10 PID setpoint Reduct. 0.0 100.0 % 10.0 1694
Defines the rate of the PID con-
troller setpoint reduction when
the Input pressure supervision
alarm is active.
V3.13.9.11 InputPress. Monitor Varies Varies Varies Varies 1695
Monitoring value for selected
Input pressure supervision sig-
nal.
Scaling value according to
P3.13.9.4.
Table 113. Input pressure supervision parameters
Code Parameter Min Max Unit Default ID Description