7.2.22 Auto-Cleaning
P3.21.1.1 C
LEANING FUNCTION
If Auto-cleaning function is enabled by parameter P3.21.1.1 the Auto-cleaning sequence will start
by activating the digital input signal selected by parameter P3.21.1.2.
P3.21.1.2 C
LEANING ACTIVATION
See above.
P3.21.1.3 C
LEANING CYCLES
The Forward/reverse cycle will be repeated for the amount of times defined by this parameter.
P3.21.1.4 C
LEAN FORWARD FREQ.
Auto-cleaning function is based on rapidly accelerating and decelerating the pump. The user can
define a forward/reverse cycle by setting parameters P3.21.1.4, P3.21.1.5, P3.21.1.6 and P3.21.1.7.
P3.21.1.5 C
LEAN FORWARD TIME
See parameter P3.21.1.4 Clean Forward Freq. above.
P3.21.1.6 C
LEAN REVERSE FREQ.
See parameter P3.21.1.4 Clean Forward Freq. above.
P3.21.1.7 C
LEAN REVERSE TIME
See parameter P3.21.1.4 Clean Forward Freq. above.
P3.21.1.8 C
LEANING ACCELERATION TIME
The user can also define separated acceleration and deceleration ramps for the Auto-cleaning
function with parameters P3.21.1.8 and P3.21.1.9.
P3.21.1.9 C
LEANING DECELERATION TIME
See parameter P3.21.1.8 Cleaning acceleration time above.
Figure 69. Auto-cleaning functionality
Zero Frequency
Output Frequency
Cleaning Forward Frequency
Cleaning Reverse Frequency
Cleaning
Forward Time
Cleaning Activation
Cleaning
Reverse Time
Cleaning Function
Cycle 1 Cycle 2
Cleaning Cycles
9139.emf