7.1.14 Group 3.13: PID Controller
7.1.14.1 Group 3.13.1: Basic Settings
Table 105. PID controller 1 basic settings
Code Parameter Min Max Unit Default ID Description
P3.13.1.1 Gain 0.00 1000.00 % 100.00 118
If the value of the parameter is set
to 100% a change of 10% in the
error value causes the controller
output to change by 10%.
P3.13.1.2 Integration Time 0.00 600.00 s 1.00 119
If this parameter is set to 1,00s a
change of 10% in the error value
causes the controller output to
change by 10.00%/s.
P3.13.1.3 Derivation Time 0.00 100.00 s 0.00 132
If this parameter is set to 1,00s a
change of 10% in the error value
during 1.00 s causes the controller
output to change by 10.00%.
P3.13.1.4 ProcessUnitSel. 1 38 1 1036 Select unit for actual value.
P3.13.1.5 ProcessUnitMin Varies Varies Varies 0 1033
Value in Process units at 0% feed-
back or setpoint.
This scaling is done for monitoring
purpose only. The PID controller
still uses the percentage internally
for feedbacks and setpoints.
P3.13.1.6 ProcessUnitMax Varies Varies Varies 100 1034 See above.
P3.13.1.7 ProcessUnitDeci 0 4 2 1035
Number of decimals for process
unit value
P3.13.1.8 Error inversion 0 1 0 340
0 = Normal (Feedback < Setpoint -
> Increase PID output)
1 = Inverted (Feedback < Setpoint -
>
Decrease PID output
)
P3.13.1.9 Dead Band Varies Varies Varies 0 1056
Dead band area around the set-
point in process units.The PID out-
put is locked if the feedback stays
within the deadband area for a
predefined time.
P3.13.1.10 Dead Band Delay 0.00 320.00 s 0.00 1057
If the feedback stays within the
dead band area for a predefined
time, the output is locked.