vacon • 84 Monitoring menu
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6.1.5 Extras & advanced
Table 50. Advanced values monitoring
Code Monitoring value Unit Scale ID Description
V2.6.1 DriveStatusWord 1 43
Bit coded word
B1=Ready
B2=Run
B3=Fault
B6=RunEnable
B7=AlarmActive
B10=DC Current in stop
B11=DC Brake Active
B12=RunRequest
B13=MotorRegulatorActive
V2.6.2 Ready status 1 78
Bit coded information about ready criteria. Useful
for debugging when the drive is not in ready sta-
tus.
Values are visible as checkboxes on graphical
keypad. If checked (), the value is active.
B0: RunEnable high
B1: No fault active
B2: Charge switch closed
B3: DC voltage within limits
B4: Power manager initialized
B5: Power unit is not blocking start
B6: System software is not blocking start
V2.6.3 Appl.StatusWord1 1 89
Bit coded statuses of application.
Values are visible as checkboxes on graphical
keypad. If checked (), the value is active.
B0=Interlock 1
B1=Interlock 2
B2=Reserved
B3=Ramp 2 active
B4=Mechanical brake control
B5=I/O A control active
B6=I/O B control active
B7=Fieldbus Control Active
B8=Local control active
B9=PC control active
B10=Preset frequencies active
B11=Inching active
B12=Fire Mode active
B13=Motor Preheat active
B14=Forced stop active
B15=Drive stopped from keypad
V2.6.4 Appl.StatusWord2 1 90
Bit coded status of application.
Values are visible as checkboxes on graphical
keypad. If checked (), the value is active.
B0=Acc/Dec prohibited
B1=Motor switch open
B5=Jockey pump active
B6=Priming pump active
B7=Input pressure supervision (Alarm/Fault)
B8=Frost protection (Alarm/Fault)
B9=Autocleaning active
V2.6.5 DIN StatusWord1 1 56
16-bit word where each bit represents the status
of one digital input. 6 digital inputs from every slot
are read. Word 1 starts from input 1 in slot A (bit0)
and goes all the way to input 4 in slot C (bit15).