7.1.14.6 Group 3.13.6: Feedback Superv.
Process supervision is used to control that the PID Feedback value (process actual value) stays
within predefined limits. With this function you can e.g. detect a major pipe burst and stop unnec-
essary flooding. See more on page 172.
7.1.14.7 Group 3.13.7: Press.Loss.Comp.
P3.13.5.7 SP 2 WakeUpLevel Varies 0.00 1077
Defines the level for the PID
feedback value wake-up super-
vision. Uses selected process
units.
P3.13.5.8 SP 2 WakeUpMode 0 1 0 1020
Select if wake up level should
work as an absolute level or as
an offset below the actual set-
point value.
0 = Absolute Level
1 = Relative Setpoint
Table 110. Process supervision parameters
Code Parameter Min Max Unit Default ID Description
P3.13.6.1 Enable Superv 0 1 0 735
0 = Disabled
1 = Enabled
P3.13.6.2 Upper limit Varies Varies Varies Varies 736
Upper actual/process value
supervision
P3.13.6.3 Lower limit Varies Varies Varies Varies 758
Lower actual/process value
supervision
P3.13.6.4 Delay 0 30000 s 0 737
If the desired value is not reached
within this time a fault or alarm is
created.
P3.13.6.5 Supervision Fault 0 3 2 749
0 = No action
1 = Alarm
2 = Fault (Stop according to stop
mode)
3 = Fault (Stop by coasting)
Table 111. Pressure loss compensation parameters
Code Parameter Min Max Unit Default ID Description
P3.13.7.1 Enable SP 1 0 1 0 1189
Enables pressure loss compen-
sation for setpoint 1.
0 = Disabled
1 = Enabled
P3.13.7.2 SP 1 Max Comp. Varies Varies Varies Varies 1190
Value added proportionally to the
frequency.
Setpoint compensation = Max
compensation * (FreqOut-Min-
Freq)/(MaxFreq-MinFreq)
P3.13.7.3 Enable SP 2 0 1 0 1191 See P3.13.7.1.
P3.13.7.4 SP 2 Max Comp. Varies Varies Varies Varies 1192 See P3.13.7.2.
Table 109. Sleep function settings