EasyManua.ls Logo

Vacon 100 INDUSTRIAL - Page 143

Vacon 100 INDUSTRIAL
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters vacon • 143
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Figure 39. Motor switch
P3.1.2.7 LOAD DROOPING
The drooping function enables speed drop as a function of load. This parameter sets that amount
corresponding to the nominal torque of the motor.
This function is used e.g. when balanced load is needed for mechanically connected motors or dy-
namic speed drooping is needed because of changing load.
E.g. if load drooping is set to 10% for a motor with a nominal frequency of 50 Hz and the motor is
loaded with nominal load (100% of torque) the output frequency is allowed to decrease 5 Hz from
the frequency reference.
Figure 40. Load drooping
M
0
1
Motor
Mains
Motor
Switch
9209.emf
Torque
Actual Speed [rpm]
Load Drooping Time
(ID656)

Table of Contents

Other manuals for Vacon 100 INDUSTRIAL

Related product manuals