EasyManua.ls Logo

Vacon 100 INDUSTRIAL - Page 167

Vacon 100 INDUSTRIAL
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters vacon • 167
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Figure 60. Setting of minimum load
P3.9.4.4 TIME LIMIT
This time can be set between 2.0 and 600.0 s.
This is the maximum time allowed for an under load state to exist. An internal up/down counter
counts the accumulated under load time. If the under load counter value goes above this limit the
protection will cause a trip according to parameter P3.9.4.1). If the drive is stopped the under load
counter is reset to zero. See Figure 61.
Figure 61. Under load time counter function
Par.
ID714
9131.emf
Par.
ID715
f
5 Hz
Underload area
Torque
Fieldweakening
point
Par. ID716
9132.emf
Trip area
Time
Underload time counter
Underload•
No underl.
Trip/warning
par. ID713

Table of Contents

Other manuals for Vacon 100 INDUSTRIAL

Related product manuals