Startup vacon • 43
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
P1.34.4 FB 1 Source 0 20 2 334
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI5
6 = AI6
7 = ProcessDataIn1
8 = ProcessDataIn2
9 = ProcessDataIn3
10 = ProcessDataIn4
11 = ProcessDataIn5
12 = ProcessDataIn6
13 = ProcessDataIn7
14 = ProcessDataIn8
15 = Temperature input 1
16 = Temperature input 2
17 = Temperature input 3
18 = Temperature input 4
19 = Temperature input 5
20 = Temperature input 6
AI’s and ProcessDataIn are
handled as % (0.00-
100.00%) and scaled accord-
ing to Feedback min and
max.
NOTE: ProcessDataIn use
two decimals.
P1.34.5 SP 1 Source 0 22 1 332
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
17 = Temperature input 1
18 = Temperature input 2
19 = Temperature input 3
20 = Temperature input 4
21 = Temperature input 5
22 = Temperature input 6
AI’s and ProcessDataIn are
handled as percent (0.00-
100.00%) and scaled accord-
ing to Setpoint minimum
and maximum. NOTE: Pro-
cessDataIn signals use 2
decimals.
P1.34.6 Keypad SP 1 Varies Varies Varies 0 167
Table 18. PID Control start-up wizard menu