User interfaces vacon • 69
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Figure 29. Programming digital inputs with text keypad
Now, the function External fault close is controlled with a digital signal to digital input DI6 (terminal
16).
Table 31. Programming digital inputs
PROGRAMMING INSTRUCTIONS
Graphical keypad Text keypad
1. Select the parameter and push the
Arrow
right
button.
1. Select the parameter and push the
OK button.
2. You are now in the
Edit mode as the slot
value
DigIN SlotA. is blinking and under-
lined. (Should you have more digital inputs
available in your I/O, for example, through
inserted option boards in slots D or E, they
can also be selected here.).
2. You are now in the
Edit mode as the letter d is
blinking. (Should you have more digital inputs
available in your I/O, for example, through
inserted option boards in slots D or E, they can
also be selected here.).
3. Push the
Arrow right button again to acti-
vate the terminal value
3.
3. Push the
Arrow right button to activate the
terminal value
3. The letter d stops blinking.
4. Push the
Arrow up button three times to
change the terminal value to
6. Confirm with
OK button.
4. Push the
Arrow up button three times to
change the terminal value to
6. Confirm with
OK button.
5. NOTE! If the digital input DI6 was already
used for some other function a message is
displayed. You might then want to change
either of these selections.
5. NOTE! If the digital input DI6 was already used
for some other function a message will scroll
through the display. You might then want to
change either of these selections.
NOTE!
The function is not assigned to any terminal, or, the the input is set to be always FALSE,
if its value is
DigIN Slot0.1 (graphical keypad) or dI 0.1 (text keypad). This is the default
value of the majority of parameters in group M3.5.1.
On the other hand, some inputs have been by default set to be always TRUE. Their value
shows
DigIN Slot0.2 (graphical keypad) or dI 0.2 (text keypad).
NOTE! Also Time Channels can be assigned to digital inputs. See more information on page 119.