Parameters vacon • 97
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
P3.2.10 Rem to Loc Funct 0 2 2 181
Choose whether to copy the
Run state and Reference when
changing from Remote to Local
(keypad) control:
0 = Keep Run
1 = Keep Run & Reference
2 = Stop
P3.2.11 Start Analogue Signal 0 1 0 1810
0= AI1
1= AI2
P3.2.12 Start Analogue Level 0.00 100.00 % 10.00 1857
Start is set below this level
(unscaled signal). Start-stop
logic is reversed if > P3.2.13
P3.2.13 Stop Analogue Level 0.00 100.00 % 80.00 1856
Start is set above this level
(unscaled signal). Start-stop
logic is reversed if < P3.2.12
Table 64. Start/Stop Setup menu
Code Parameter Min Max Unit Default ID Description