Power cabling vacon • 40
Service support: find your nearest Vacon service center at www.vacon.com
4
Tightening torques of cable glands:
UL installation:
Figure 27.Cable entry plate, MM4 UL installation.
Frame
Gland screw
type [metric]
Tightening torque [Nm]/[lb-in.]
[Nm] lb-in.
MM4
M16 1.0 8.9
M25 4.0 35.5
MM5
M16 1.0 8.9
M25 4.0 35.5
M32 7.0 62.1
MM6
M16 1.0 8.9
M25 4.0 35.5
M40 10.0 88.7
Table 15. Tightening torque and dimension of cable glands.
6
• To connect NPT pipes to Vacon
®
100X, use the optional metal cable entry plate
(included in -R02 option) to meet UL installation rules.
• One metal conduit plate with accessories (screws and gasket) is delivered in a
separate bag together with the drive. See the following figures for more
details.