Technical data vacon •
Service support: find your nearest Vacon service center at www.vacon.com
7
Table 29. VACON
®
100 X technical data.
Declaration of Con-
formity
Korea KC mark
Australia C-tick Declaration of Conformity
Europe EC Declaration of Conformity
Protections
Undervoltage trip limit
Depends on supply voltage (0,8775*supply volt-
age):
Supply voltage 400 V: Trip limit
351 V
Supply voltage 480 V: Trip limit 421 V
Supply voltage 240 V: Trip limit 211 V
Overvoltage fault protec-
tion
Yes
Earth fault protection Yes
Mains supervision Yes
Motor phase supervision Yes
Overcurrent protection Yes
Unit overtemperature
protection
Yes
Motor overload protec-
tion
Yes. These devices provide motor overeload pro-
tection at 105% of full load amperes.
Motor stall protection Yes
Motor underload protec-
tion
Yes
Short-circuit protection
of +24V and +10V refer-
ence voltages
Yes
Thermal motor protec-
tion
Yes (by PTC)