Why is PRESSURE CONTROL not optimal on VAT 612?
- NNicholas SharpAug 30, 2025
To optimize PRESSURE CONTROL on your VAT Control Unit, perform the setup procedure completely, perform LEARN, and ensure ZERO was performed before LEARN. Repeat LEARN if it was interrupted or if the gas flow was unstable. Tune the valve for your application and verify the sensor range is suitable. Also, ensure a shielded sensor cable is used. These steps address potential issues such as incomplete setup, improper LEARN execution, unstable gas flow, incorrect tuning, unsuitable sensor range, or noise on the sensor signal.