INSTALLATION
Series 612
Edition 2013-04-12
601894EA
Inquiry function
Command
Acknowledgement
(within 10ms after reception of command)
Description
THROTTLE CYCLE
COUNTER
Get
[i:70][CR][LF]
[i:70][xxxxxxxxxx][CR][LF]
data length 10 characters
xxxxxxxxxx number of throttle cycles
This function returns the number of throttle cycles. A movement from max. throttle position
to open back to max. throttle position counts as one cycle. Partial movements will be
added up until equivalent movement is achieved.
POWER UP COUNTER
Get
[i:72][CR][LF]
[i:72][xxxxxxxxxx][CR][LF]
data length 10 characters
xxxxxxxxxx number of power ups
This function returns the number of control unit power ups.
HARDWARE
CONFIGURATION
Get
[i:80][CR][LF]
[i:80][abcdefgh][CR][LF]
data length 8 characters
a 0 = Power Failure Option (PFO) not equipped
1 = Power Failure Option (PFO) equipped
b 0 = ±15V sensor power supply (SPS) not equipped
1 = ±15V sensor power supply (SPS) equipped
c 2 = RS232 Interface without analog outputs
3 = RS232 Interface with analog outputs
d 1 = 1 sensor version, 2 = 2 sensor version
efgh reserved, do not use
This function returns the hardware configuration of the device.
FIRMWARE
CONFIGURATION
Get
[i:82][CR][LF]
[i:82][xxxxxxxx][CR][LF]
data length 8 characters
xxxxxxxx firmware version, e.g. 612P1E00
This function returns firmware version of the device.
IDENTIFICATION
Get
[i:83][CR][LF]
[i:83][xxxxxxxxxxxxxxxxxxxx][CR][LF]
data length 20 characters
xxx...xxx identification code, e.g. 61228-KAGG-0002/0001/, unused digits are filled up
with spaces (20 hexadecimal)
This function returns controller's individual serial number. This code is unique for each
valve and allows tracing.