DSGH Installation and Operation Guide 43
Calibration
placement of a resistor across terminals 13 and 14. Hook the meter or
DCS in series with the load resistor.
Procedure 3.1: To calibrate the current loop
1. Select Calibration | Current Loop Cal.
2. Click Execute.
3. Click OK.
4.
Read the ammeter; enter the actual milliamp reading.
5. Click OK.
6. Click YES if the ammeter reads 4.00 mA or NO for any other reading.
7. Repeat until the meter reads 4.00 mA. The meter
approaches the 4.00 mA successively.
8. Read the ammeter; enter the actual milliamp reading.
Note: If using a voltmeter, calculate the current value.