9 Set up with the display and adjustment module
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66190-EN-221107
•
Measurement reliability
•
Electronics temperature
•
Measuring rate
•
Operating voltage
Here you determine which heights of the output value belong to the
current values 4 mA and 20 mA .
Note:
This menu item is only available if one of the following output values
was selected for the current output:
•
Measurement reliability
•
Electronics temperature
•
Measuring rate
•
Operating voltage
In the menu item " Current output - Output characteristic" you select
for 0 … 100 % output value if the characteristic of the current output
rises (4 … 20 mA) or falls (20 … 4 mA).
In the menu item " Current output - Current range" you determine the
range of the current output as 4 … 20 mA or 3.8 … 20.5 mA.
In the menu item " Current output - Behaviour in case of failure" you
setthebehaviourofthecurrentoutputincaseoffailuresas≤3.6mA
or≥21mAresp.thelastmeasuredvalue.
Linearisation is required for all vessels where the vessel volume does
not increase linearly with the level and the display or output of the
Current output - Initial/Fi-
nal value characteristics
Current output - Output
characteristics
Current output - Current
range
Current output - Reaction
in case of fault
Linearisation