9 Set up with the display and adjustment module
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66190-EN-221107
HART address deviation from 0:
In the menu item " Output mode" " Fixed current (4 mA)" is displayed
andindependentoftheactuallevelaxed4mAsignaloutput.The
level is output digitally via the HART signal.
In the mode " Fixed current" up to 63 sensors can be operated on one
two-wire cable (Multidrop operation). An address between 0 and 63
must be assigned to each sensor.
This menu item contains operational settings of the sensor.
Mode:
Countryspecicsettingsfortheradarsignalsaredeterminedviathe
operating mode.
•
Mode 1: EU, Albania, Andorra, Azerbaijan, Australia, Belarus, Bos-
nia and Herzegovina, Canada, Liechtenstein, Moldavia, Monaco,
Montenegro, New Zealand, Northern Macedonia, Norway, San
Marino, Saudi Arabia, Serbia, Switzerland, Turkey, Ukraine, United
Kingdom, USA
•
Mode of operation 2: Brazil, Japan, South Korea, Taiwan, Thailand
•
Mode of operation 3: India, Malaysia, South Africa
•
Mode of operation 4: Russia, Kazakhstan
Note:
Depending on the operating mode, metrological properties of the
device can change (see chapter " Technical data, input variable").
Voltage supply:
The power supply determines whether the sensor is in operation
permanently or only in accordance with certain requirements.
The following functions are available:
Load from sensor:
Store data from sensor in the display and adjustment module.
Mode
Copy instrument settings