Chapter 9 Product Specifications
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
Chapter 9 Product Specifications
9.1 CONFORMITY AND STANDARDS
The UPS has been designed to conform to the following European and international standards:
Standards and Directives:
Item Normative reference
Low Voltage Directive
2006/95/EC with the Amendment Directive 93/68/EEC Directive for
electromagnetic compatibility 2004/108/EC
General and safety requirements for UPS
used in operator access areas
IEC/EN 62040-1 incorporating requirements of IEC/EN 60950-1
Electromagnetic compatibility (EMC)
requirements for UPS
IEC/EN 62040-2: Immunity category C2, Emission category C2
Tab.
9-1: Compliance with European, international standards
The above mentioned product standards incorporate relevant compliance clauses with generic IEC and EN standards
for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/ AS61000 series) and construction
(IEC/EN/AS60146 series and 60529). The APM output dynamic performances conforms the IEC62040-3 Class 3.
9.2 PRODUCT SPECIFICATIONS
Item Unit 30kW 90kW 150kW
Acoustic noise level at 1 meter
full load
dB <53dBA <58dBA <62dBA
Acoustic noise level at 1 meter
half load
dB <52dBA <56dBA <58dBA
Altitude of Operation m
1000m above sea level, derate power by 1% per 100m between 1000m
and 2000m
Relative Humidity - 0 to 95% non condensing
Operating Temperature °C 0 to 40°C *; Note: Battery life is halved for every 10°C increase above 20°C
UPS Storage-Transport
Temperature
°C -20~70
Recommended Battery Storage
Temperature
°C -20°C to 30°C (20°C for optimum battery storage)
Tab.
9-2:
Environmental parameters
Conditions apply
AC/AC Efficiency Unit Data
Rated Power kVA 30~150
Normal mode ¹ (dual conversion)
% 96
Battery Mode 
$
% 96
Heat Losses & Air Exchange
Rated Power kVA 30 60 90 120 150
Normal Mode kW 1.2 2.4 3.6 4.8 6
No Load kW 0.6 1.2 1.8 2.4 3
Maximum forced air cooling (front
intake, rear exhaust)
L/sec 48 96 144 192 239
Tab.
9-3: AC/AC Efficiency, Loss and Air Exchange
1) 400Vac input and output, battery fully charged, full-rated linear load.
2) Inverter Efficiency (DC/AC), battery at nominal voltage 432VDC and full-rated linear load