UNIT SIZE, TYPE
10 BAY 16 BAY 12 BAY 16 BAY 10 BAY 16 BAY
NO TRANSFORMER TRANSFORMER-BASED NO TRANSFORMER DUAL INVERTER
FRAME RATING,
KVA/KW
15/13.5 20/18 15/13.5 20/18 15/13.5 20/18
Output Overload
Capability
< 104% continuous
105% - 130% for 1 min
131% - 150% for 10 sec
151% - 200% for 1 sec
> 201% for 250 msec
Table 8.1 Liebert APS specifications (continued)
SYSTEM CONFIGURATION % UPS LOAD LOW LIMIT VALUE HIGH LIMIT VALUE
Dual-Inverter
Configured to 120
or 127 VAC per Phase
>100% 98 ±3.1
139.5 ±3.1
90% ~ 100% 89 ±3.1 ~ 98 ±3.1
70% ~ 90% 74 ±3.1 ~ 89 ±3.1
30% ~ 70% 60.5 ±3.1 ~ 74 ±3.1
<30% 60.5 ±3.1
Dual-Inverter
Configured to 100,
110 or 115 VAC per Phase
>100% 84 ±3.1
90% ~ 100% 80 ±3.1 ~ 84 ±3.1
70%~90% 72 ±3.1 ~ 80 ±3.1
40%~70% 60 ±3.1 ~ 72 ±3.1
<40% 60 ±3.1
Single-Inverter
Transformer-Based and
Transformer-Free
>100% 170 ±5
280 ±5
90% ~ 100% 160 ±5 ~ 170 ±5
70%~90% 140 ±5 ~ 160 ±5
50%~70% 120 ±5 ~ 140 ±5
<50% 120 ±5
Table 8.2 Rated input voltage range (Unit: VAC)
PARAMETERS AS7EBCNCC1BX000
General and Environmental
Conducted and Radiated EMC Levels IEC/EN/AS 62040-2—Class A, FCC Part 15 (Class A)
Safety Standards IEC/EN/AS 62040-1:2008, UL 1778 5
th
Ed and CSA 22.2 No. 107.3
Immunity Standards IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Table 8.3 Liebert APS external battery cabinet specifications
Vertiv | Liebert® APS™ Installer/User Guide | 83