EasyManua.ls Logo

Vertiv Liebert CRV Plus - Model Nomenclature; Basic Performance Parameters

Vertiv Liebert CRV Plus
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vertiv | Liebert CRV+ | User Manual 2
1.1 Model Nomenclature
The model nomenclature of the CRV+ air cooled unit is shown in Figure 1-2:
1
2
3
4
5
6
7
8
9
11
12
14
15
16
17
18
19
20
21
22
23
25
C
R
0
2
5
H
A
1
3
8
O
S
0
2
E
1
0
0
0
0
C
V
0
0
0
Bit 1 and Bit 2 Product Model Bit 14 Filter
CR Liebert CRV+
0
Bit 3 ~ Bit 5 Series Name Description
2
025 Nominal Capacity
G4 with filter clogged switch
G4
Bit 6 Air Discharge
Bit 15 Coil and value
R Horizontal supply with guide grill
E
H
Horizontal supply without guide grill
Standard DX Air Cooled Coiled &
Electronic Expansion Valve (EEV)
Bit 7 System Type
Bit 16 Cabinet Color
A
Air cooled
1 Standard color ( Z-7021 black-grey)
Bit 8Airflow
Bit 17 High Pressure Option
1 EC Fan
0 None
Bit 9 Power Supply
Bit 18 Low Voltage Locking Option
3 380-415V/3 ph/50Hz +N
0 None
T 380/3 ph/60Hz +N
Bit 19 Monitor
Bit 10 System Configuration
0 None
S SIC Card
Bit 20 Detector
8 R-410A brushless scroll compressor
0 None
Bit 11 Humidifier
Bit 21 Package
0 None
P Domestic
S Electrode humidifier
C Overseas (sea worthy)
Bit 12 Display
Bit 22 Special Function
L Large Display
A None
S Standard display panel
V
With condensate drain pump
Bit 13 Heating
0
1
None
Electrical heater
Figure 1-2 Model Nomenclature
1.2 Basic Performance Parameters
The basic performance parameters of the Liebert CRV+ AC series are given in Table within Listing 1.1.
Listing 1.1
Model
Nominal cooling
capacity (kW)
Power
(kW)
Heating capacity
(kW)
Humidification
capacity (kg/h)
CR012 13.6 3.3 2 /
CR025
20.8
6.1
3
1.5
CR035 38.1 10.1 5.5 1.5
Condition: Return air 37˚C, 24%RH & 45˚C condensing temperature
Bit 23~25 Special Identifier for order
0
None

Table of Contents