Vertiv | Liebert CRV+ | User Manual 2
1.1 Model Nomenclature
The model nomenclature of the CRV+ air cooled unit is shown in Figure 1-2:
E
Bit 1 and Bit 2 Product Model Bit 14 Filter
0
Bit 3 ~ Bit 5 Series Name Description
2
025 Nominal Capacity
G4 with filter clogged switch
G4
Bit 15 Coil and value
R Horizontal supply with guide grill
E
H
Horizontal supply without guide grill
Standard DX Air Cooled Coiled &
Electronic Expansion Valve (EEV)
Bit 16 Cabinet Color
Air cooled
1 Standard color ( Z-7021 black-grey)
Bit 17 High Pressure Option
0 None
Bit 18 Low Voltage Locking Option
0 None
Bit 19 Monitor
Bit 10 System Configuration
0 None
S SIC Card
Bit 20 Detector
8 R-410A brushless scroll compressor
0 None
Bit 11 Humidifier
Bit 21 Package
0 None
P Domestic
S Electrode humidifier
C Overseas (sea worthy)
Bit 12 Display
Bit 22 Special Function
L Large Display
A None
S Standard display panel
V
With condensate drain pump
Bit 13 Heating
0
1
None
Electrical heater
Figure 1-2 Model Nomenclature
1.2 Basic Performance Parameters
The basic performance parameters of the Liebert CRV+ AC series are given in Table within Listing 1.1.
Listing 1.1
Model
Nominal cooling
capacity (kW)
Power
(kW)
Heating capacity
(kW)
Humidification
capacity (kg/h)
CR012 13.6 3.3 2 /
CR035 38.1 10.1 5.5 1.5
Condition: Return air 37˚C, 24%RH & 45˚C condensing temperature
Bit 23~25 Special Identifier for order
0
None