EasyManua.ls Logo

Vertiv Liebert CRV Plus - Air Filter Maintenance

Vertiv Liebert CRV Plus
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vertiv | Liebert CRV+ | User Manual 73
Water leak Detector
Lay water leak detectors and confirm the alarm information through the controller. The detector should be
located away from any water pool or drainage trench on the floor, 2 to 2.5 meters away from the unit. Do
not place it directly under the machine.
Figure 3-37 shows the recommended location for the water leak detector:
Figure 3-37 Recommended location for the water leak detector
Ensure that the power supply of the control unit has been disconnected before connecting
any mechanical parts or cables.
Do not use the water leak detector in the vicinity of flammable liquids; do not use it to
detect any flammable liquids.
3.2.5 Air Filter Maintenance
The efficiency of the configured filter is 30%, in compliance with industry standards such as the America
ASHRAE52-76 and Eurovent 4/5 standard; the dust resistance value is 90% (EU4 standard).
Set the filter maintenance and alarm logic to ensure efficient operation. The fan operating time is
2160 hours by default (though the time is set and customized based on the local operating
environment); the filter maintenance alarm is triggered based on the configuration and settable
operation time.
Check and replace the filter according to its dust and clogging condition. During normal
operations, the filter needs to be checked once a month and replaced as per the requirement.
Cut off the power before replacing the filter. Clear the fan operating time after replacing the
filter.
Liebert unit
Drain pipes on the ground
Location of water
leak detector
Location of water
leak detector