Vertiv | Liebert CRV+ | User Manual 9
1.5 Working Conditions
In this section, take a look at the environmental conditions including the Operating and Storage
environment.
1.5.1 Operating Environment
The table in Listing 1.3 defines the Operating environment parameters including the Ambient
Temperature, Protection level, Altitude, and Voltage range.
Listing 1.3
Ambient temperature
Indoor 18°C ~ 40°C
Outdoor
CR012: -15°C ~ +45°C, if a low temperature kit is
configured, the lowest outdoor operation
temperature is -34°C
CR025 and CR035: -20°C ~ +45°C, if a low
temperature kit is configured, the lowest outdoor
operation temperature is -34°C
Protection level (indoor unit) IP20
Altitude < 1000m. Above that, please contact Vertiv Co.
Operation voltage range (380 ~ 415)V ± 10%, 3N ~ 50Hz / 60Hz
1.5.2 Storage Environment
The following table in Listing 1.4 defines the Storage Environment parameters including the ambient
humidity, ambient temperature, and storage time conditions.
Listing 1.4
Indoor, clean (without dust)
Ambient humidity < 95%RH
Storage time
Total transportation and storage time should not exceed six months.
Otherwise, the performance needs to be re-calibrated